Bus node CTEU-PN (2201471)

2201471 CTEU-PN
Reference 2201471
Type code CTEU-PN
Festo
7 units
In Stock
€359.45
Tax excluded
Bus node

Description of Bus node CTEU-PN (2201471)

Dimensions W x L x H40 mm x 91 mm x 50 mm
Type of mountingOn electrical interface On electrical sub-base
KC charactersKC EMC
Fieldbus interface, protocolPROFINET RT
Power supply, functionElectronics and load
Power supply, connection technologyM12x1, A-coded as per EN 61076-2-101
Power supply, type of connectionPlug
Fieldbus interface, typeEthernet
Fieldbus interface, functionBus connection, incoming/forwarding
Fieldbus interface, transmission rate100 Mbit/s
Fieldbus interface, galvanic isolationyes
Fieldbus interface, connection pattern00995716
Power supply, connection pattern00995383
Fieldbus interface, connection technologyM12x1, D-coded as per EN 61076-2-101
Fieldbus interface, connection type2x socket
Note on degree of protectionIn mounted state Unused connections sealed
Fieldbus interface, number of poles/wires4
Power supply, number of pins/wires5
Width dimension40 mm
Type codeCTEU
DiagnosticsCommunication error System diagnostics Undervoltage
Configuration supportGSDML file
Additional functionsConformance class C Fast start-up (FSU) LLDP MRP PROFINET IRT PROFIenergy SNMP Shared device Web server
Internal cycle time1 ms per 1 byte of user data
DC operating voltage range18 V ... 30 V
Intrinsic current consumption at nominal operating voltageTyp. 80 mA
Max. power supply4 A
Nominal operating voltage DC24 V
ProtocolPROFINET
CE marking (see declaration of conformity)As per EU EMC directive
Corrosion resistance class (CRC)2 - Moderate corrosion stress
Storage temperature-20 °C ... 70 °C
Degree of protectionIP65 IP67
Ambient temperature-5 °C ... 50 °C
CertificationRCM compliance mark c UL us - Listed (OL)
Product weight93 g
Max. address capacity outputs64 byte
Max. address capacity inputs64 byte
LED display (bus-specific)NF: network fault TP1: network active port 1 TP2: network active, port 2
LED display (product-specific)PS: operating voltage for electronics and load supply X1: module system status at I-Port 1 X2: module system status at I-Port 2
Note on materialsContains paint-wetting impairment substances RoHS-compliant
Housing materialPA

Details of Bus node CTEU-PN (2201471)

Type code
CTEU-PN
gtin
4052568264444
2201471
7 Items
New
Producto añadido al comparador.