Dimensions W x L x H | (incl. interlinking block and connection system) 50 mm x 107 mm x 50 mm |
Type code | CPX |
No. of inputs | 2 |
Diagnostics | Wire break per channel Limit value violation per channel Short circuit, input signal Parameterization error |
Parameterization | Data format Forcing per channel Limit value monitoring per channel Measured value smoothing Signal range per channel Response to short circuit Wire break monitoring per channel |
LED indicators | 1 group diagnostics |
Internal cycle time | 4 ms |
Repetition accuracy | 0.15 % at 25 °C |
Fuse protection (short circuit) | Internal electronic fuse |
DC operating voltage range | 18 V ... 30 V |
Intrinsic current consumption at nominal operating voltage | Typ. 50 mA |
Operating error limit related to the ambient temperature range | +/- 0.5 % for voltage inputs |
Basic error limit at 25°C | +/- 0.3 % for voltage inputs |
Nominal operating voltage DC | 24 V |
Electrical isolation between channel and internal bus | Yes, without using the internal sensor supply |
Electrical isolation between channels | no |
Corrosion resistance class (CRC) | 1 - Low corrosion stress (when installed) |
Storage temperature | -20 °C ... 70 °C |
Degree of protection | Depends on manifold block |
Ambient temperature | -5 °C ... 50 °C |
Product weight | 48 g |
Data format | 12 bit + sign Scalable to 15 bits |
Max. cable length | 30 m Shielded |
Sensor type | 0 - 10 V 0 - 20 mA 4 - 20 mA |
Housing material | PA-reinforced PC |