Your cart
There are no more items in your cart
Dimensions W x L x H | (incl. interlinking block and connection system) 50 mm x 107 mm x 50 mm |
Type code | CPX |
No. of outputs | 2 |
Diagnostics | Wire break per channel Limit value violation per channel Output signal short circuit per channel Actuator supply short circuit Parameterization error Undervoltage of outputs |
Parameterization | Data format Fail-safe modes per channel Forcing per channel Limit value monitoring per channel Idle mode per channel Measured value smoothing Signal range per channel Response to short circuit Wire break monitoring per channel |
LED indicators | 1 group diagnostics |
Internal cycle time | 4 ms |
Repetition accuracy | 0.05 % at 25 °C |
Fuse protection (short circuit) | Internal electronic fuse |
DC operating voltage range | 18 V ... 30 V |
Intrinsic current consumption at nominal operating voltage | Typ. 100 mA |
Operating error limit related to the ambient temperature range | ±0.6 % |
Basic error limit at 25°C | ±0.5 % |
Nominal operating voltage DC | 24 V |
Electrical isolation between channel and internal bus | Yes, without using the internal sensor supply |
Electrical isolation between channels | no |
Corrosion resistance class (CRC) | 1 - Low corrosion stress (when installed) |
Storage temperature | -20 °C ... 70 °C |
Degree of protection | Depends on manifold block |
Ambient temperature | -5 °C ... 50 °C |
Product weight | 49 g |
Data format | 12 bit + sign Scalable to 15 bits |
Max. cable length | 30 m Shielded |
Sensor type | 0 - 10 V 0 - 20 mA 4 - 20 mA |
Housing material | PA-reinforced PC |