Dimensions W x L x H | 40 mm x 91 mm x 50 mm |
Type of mounting | On electrical interface On electrical sub-base |
KC characters | KC EMC |
Fieldbus interface, protocol | CC-LINK® |
Note on fieldbus interface | Optional connection technology with accessories: Open style (screw terminal, 5-pin, degree of protection: IP20) |
Power supply, function | Electronics and load |
Power supply, connection technology | M12x1, A-coded as per EN 61076-2-101 |
Power supply, type of connection | Plug |
Fieldbus interface, type | Serial interface |
Fieldbus interface, function | Bus connection, incoming/forwarding |
Fieldbus interface, transmission rate | 156 - 10000 kbit/s |
Fieldbus interface, galvanic isolation | yes |
Fieldbus interface, connection pattern | 00995638 |
Power supply, connection pattern | 00995383 |
Fieldbus interface, connection technology | Sub-D |
Fieldbus interface, connection type | Socket |
Note on degree of protection | In mounted state Unused connections sealed |
Fieldbus interface, number of poles/wires | 9 |
Power supply, number of pins/wires | 5 |
Width dimension | 40 mm |
Type code | CTEU |
Diagnostics | Communication error System diagnostics Undervoltage |
Additional functions | System status can be indicated via process data |
Parameterization | Activate diagnostics Fail-safe and idle response |
Control elements | DIL switch |
Internal cycle time | 1 ms per 1 byte of user data |
DC operating voltage range | 18 V ... 30 V |
Intrinsic current consumption at nominal operating voltage | Typ. 70 mA |
Max. power supply | 4 A |
Nominal operating voltage DC | 24 V |
Protocol | CC-LINK® |
CE marking (see declaration of conformity) | As per EU EMC directive |
Corrosion resistance class (CRC) | 2 - Moderate corrosion stress |
Storage temperature | -20 °C ... 70 °C |
Degree of protection | IP65 IP67 |
Ambient temperature | -5 °C ... 50 °C |
Certification | RCM compliance mark c UL us - Listed (OL) |
Product weight | 90 g |
Max. address capacity outputs | 16 byte |
Max. address capacity inputs | 16 byte |
LED display (bus-specific) | Err: data transmission error Run: bus active |
LED display (product-specific) | PS: operating voltage for electronics and load supply X1: module system status at I-Port 1 X2: module system status at I-Port 2 |
Note on materials | Contains paint-wetting impairment substances RoHS-compliant |
Housing material | PA |